Abstract
The diagnostic capability of a simple thermodynamic model for chiller performance is illustrated by a case study for a commercial, installed centrifugal chiller. Performance data were measured both prior to, and subsequent to, chiller maintenance that improved chiller efficiency. Using these experimental measurements, we show that the simple thermodynamic model, originally developed for reciprocating and absorption chillers, (1) succeeds in predicting the fundamental relation between coefficient of performance and cooling rate for the centrifugal chiller, and (2) permits a clear diagnostic analysis of heat exchanger fouling on chiller performance.
On démontre, par le biais d'une étude de cas d'un refroidisseur centrifuge commercial, déjà installé, les possibilités d'un modèle thermodynamique simple pour l'évaluation des performances des refroidisseurs. On a mesuré les données de performance avant et après une opération d'entretien qui a amélioré le rendement du refroidisseur. Avec l'appui de ces mesures expérimentales, nous montrons que le modèle thermodynamique simple, mis au point, à l'origine, pour les refroidisseurs à piston et à absorption, permet, d'une part, de prévoir la relation fondamentale entre le coefficient de performance et la puissance frigorifique pour le refroidisseur centrifuge et, d'autre part, d'effectuer un diagnostic clair de l'effet de l'encrassement des échangeurs de chaleur sur la performance du refroidisseur.